University of Illinois at Urbana-Champaign
Diagnosis of arcing in retaining rings of turbogenerators
Abstract
dc:descriptionRetaining rings are an important and most highly stressed component of the entire turbogenerator system. Arcing in retaining rings is a very serious problem and could easily escalate to a full-blown failure. In this project we diagnose arcing in the retaining rings. We determine the most likely mechanism by which arcing occurs and the category of events which lead to it. Specifically, we try to test two different mechanisms which could have led to the arc marks. The first one is sparking due to high field efects (or high voltage gradient across the contact junction) and the other is a make-and-break contact arcing owing to the presence of inductance in the system. Experiments performed to measure the contact resistance between the retaining ring and mild iron piece indicate that even very high fault currents cannot produce the voltage required to cause sparking. Transient 3-D finite element simulations show that a make-and-break contact can generate localized voltage spikes, on account of small contact break, which are high enough to lead to arcing. Interestingly this can happen at relatively low currents.
Degree
thesis:*- Name thesis:degree_name
- M.S.
- Level thesis:degree_level
- Thesis
- Discipline thesis:degree_discipline
- Electrical & Computer Engr
- Grantor
- University of Illinois at Urbana-Champaign
- Year dc:date
- 2016
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Harmukh, Sajal Kumar
- Contributors dc:contributor
-
- Haran, Kiruba Sivasubramaniam
Subjects
dc:subject × 4Rights
dc:rights- Statement dc:rights
-
- Copyright 2016 Sajal Harmukh
- Language dc:language
- en
Identifiers
dc:identifier.*- Handle dc:identifier
- http://hdl.handle.net/2142/90752
- OAI identifier oai:identifier
- oai:www.ideals.illinois.edu:2142/90752