University of Illinois at Urbana-Champaign
Airflow Analysis in Mechanically Ventilated Obstructed Rooms
Abstract
dc:descriptionIt was concluded that for typical room flowrates and inlet types the room air distribution system is obstruction ratio independent. Local velocities and standard deviations varied with each obstruction setup and inlet combination. However, average air velocities and turbulence intensities were not influenced by obstruction setups or inlet configurations. The decay rate of mean velocity kinetic energy in the bulk flow region was independent of obstructions and inlets. Room average kinetic energy was a function of the supplied kinetic energy within the supply jet plus internal kinetic energy resulting from internal heat load (convective energy).
Degree
thesis:*- Name thesis:degree_name
- Ph.D.
- Level thesis:degree_level
- Dissertation
- Discipline thesis:degree_discipline
- Agricultural Engineering
- Grantor
- University of Illinois at Urbana-Champaign
- Year dc:date
- 2015
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Priest, John Brian
- Contributors dc:contributor
-
- Christianson, Leslie L.
Subjects
dc:subject × 1Rights
- Language dc:language
- eng
Identifiers
dc:identifier.*- Identifier
- (MiAaPQ)AAI9953114
- OAI identifier oai:identifier
- oai:www.ideals.illinois.edu:2142/86097