University of Illinois at Urbana-Champaign
An assessment of fin-tube thermal contact resistance in round-tube-plain-fin heat exchangers
Abstract
dc:descriptionFin-and-tube heat exchangers are used in a wide variety of applications. Heat exchangers with expanded tubes are economical, but a drawback is the potentially large contact resistance between tubes and fins. Previous studies have investigated this topic under the exclusion of air-side convection. The present work is more realistic, because the contact resistance is evaluated in the presence of air-side convection. The goal of this experimental work is to determine the contribution of the contact resistance to the overall heat transfer resistance in round-tube-plain-fin heat exchangers. The four samples have copper tubes with two different expansion ratios and aluminum fins with collars of two different lengths. The heat exchangers were examined in a wind tunnel under dry and frosted conditions to determine the contact resistance. The frosted heat exchangers are used as a baseline, because frost growth bridges the gaps between fins and tubes. The contact resistance was much higher for the unexpanded heat exchangers – about 30-60% of the overall resistance, whereas expanded heat exchangers exhibited a contact resistance of about 10-30% of the overall resistance.
Degree
thesis:*- Name thesis:degree_name
- M.S.
- Level thesis:degree_level
- Thesis
- Discipline thesis:degree_discipline
- Mechanical Engineering
- Grantor
- University of Illinois at Urbana-Champaign
- Year dc:date
- 2015
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Cortes, Maria
Subjects
dc:subject × 2Rights
dc:rights- Statement dc:rights
-
- Copyright 2015 Maria Cortes
- Language dc:language
- en
Identifiers
dc:identifier.*- Handle dc:identifier
- http://hdl.handle.net/2142/78523
- OAI identifier oai:identifier
- oai:www.ideals.illinois.edu:2142/78523