System identification and optimal control for mixed-mode cooling

Abstract

dc:description.abstract

The majority of commercial buildings today are designed to be mechanically cooled. To make the task of air conditioning buildings simpler, and in some cases more energy efficient, windows are sealed shut, eliminating occupants' direct access to fresh air. Implementation of an alternative cooling strategy-mixed-mode cooling-is demonstrated in this thesis to yield substantial savings in cooling energy consumption in many U.S. locations. A mixed-mode cooling strategy is one that relies on several different means of delivering cooling to the occupied space. These different means, or modes, of cooling could include: different forms of natural ventilation through operable windows, ventilation assisted by low-power fans, and mechanical air conditioning. Three significant contributions are presented in this thesis. A flexible system identification framework was developed that is well-suited to accommodate the unique features of mixed-mode buildings. Further, the effectiveness of this framework was demonstrated on an actual multi- zone, mixed-mode building, with model prediction accuracy shown to exceed that published for other naturally ventilated or mixed-mode buildings, none of which exhibited the complexity of this building. Finally, an efficient algorithm was constructed to optimize control strategies over extended planning horizons using a model-based approach. The algorithm minimizes energy consumption subject to the constraint that indoor temperatures satisfy comfort requirements. The system identification framework was applied to another mixed-mode building, where it was found that the aspects integral to the modeling framework led to prediction improvements relative to a simple model.

Degree

thesis:*
Department dc:contributor.department
Massachusetts Institute of Technology. Dept. of Mechanical Engineering.
Grantor dc:publisher
Massachusetts Institute of Technology
Year dc:date.issued
2004

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Spindler, Henry C. (Henry Carlton), 1970-
Advisor dc:contributor.advisor
  • Leslie K. Norford.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1721.1/30334
OAI identifier oai:identifier
oai:dspace.mit.edu:1721.1/30334

Chain of custody

source
Harvested from
MIT
Base URL
dspace.mit.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Spindler, Henry C. (Henry Carlton), 1970-. System identification and optimal control for mixed-mode cooling. Massachusetts Institute of Technology, 2004. http://hdl.handle.net/1721.1/30334