{"id":{"repo_id":"mit","oai_identifier":"oai:dspace.mit.edu:1721.1/30334"},"canonical_url":"https://search.dev.ndltd.org/etd/mit/oai:dspace.mit.edu:1721.1/30334","repository":{"repo_id":"mit","name":"MIT","base_url":"https://dspace.mit.edu/oai/request"},"display":{"title":"System identification and optimal control for mixed-mode cooling","abstract":"The majority of commercial buildings today are designed to be mechanically cooled. To make the task of air conditioning buildings simpler, and in some cases more energy efficient, windows are sealed shut, eliminating occupants' direct access to fresh air. Implementation of an alternative cooling strategy-mixed-mode cooling-is demonstrated in this thesis to yield substantial savings in cooling energy consumption in many U.S. locations. A mixed-mode cooling strategy is one that relies on several different means of delivering cooling to the occupied space. These different means, or modes, of cooling could include: different forms of natural ventilation through operable windows, ventilation assisted by low-power fans, and mechanical air conditioning. Three significant contributions are presented in this thesis. A flexible system identification framework was developed that is well-suited to accommodate the unique features of mixed-mode buildings. Further, the effectiveness of this framework was demonstrated on an actual multi- zone, mixed-mode building, with model prediction accuracy shown to exceed that published for other naturally ventilated or mixed-mode buildings, none of which exhibited the complexity of this building. Finally, an efficient algorithm was constructed to optimize control strategies over extended planning horizons using a model-based approach. The algorithm minimizes energy consumption subject to the constraint that indoor temperatures satisfy comfort requirements. The system identification framework was applied to another mixed-mode building, where it was found that the aspects integral to the modeling framework led to prediction improvements relative to a simple model.","abstract_html":"The majority of commercial buildings today are designed to be mechanically cooled. To make the task of air conditioning buildings simpler, and in some cases more energy efficient, windows are sealed shut, eliminating occupants&#x27; direct access to fresh air. Implementation of an alternative cooling strategy-mixed-mode cooling-is demonstrated in this thesis to yield substantial savings in cooling energy consumption in many U.S. locations. A mixed-mode cooling strategy is one that relies on several different means of delivering cooling to the occupied space. These different means, or modes, of cooling could include: different forms of natural ventilation through operable windows, ventilation assisted by low-power fans, and mechanical air conditioning. Three significant contributions are presented in this thesis. A flexible system identification framework was developed that is well-suited to accommodate the unique features of mixed-mode buildings. Further, the effectiveness of this framework was demonstrated on an actual multi- zone, mixed-mode building, with model prediction accuracy shown to exceed that published for other naturally ventilated or mixed-mode buildings, none of which exhibited the complexity of this building. Finally, an efficient algorithm was constructed to optimize control strategies over extended planning horizons using a model-based approach. The algorithm minimizes energy consumption subject to the constraint that indoor temperatures satisfy comfort requirements. The system identification framework was applied to another mixed-mode building, where it was found that the aspects integral to the modeling framework led to prediction improvements relative to a simple model.","abstract_has_math":false,"creators":["Spindler, Henry C. (Henry Carlton), 1970-"],"institution":"Massachusetts Institute of Technology","degree_name":null,"degree_level":null,"degree_discipline":null,"degree_department":"Massachusetts Institute of Technology. Dept. of Mechanical Engineering.","school":null,"contributors":[],"advisors":["Leslie K. Norford."],"committee_chairs":[],"committee_members":[],"year":2004,"date_issued":"2004","date_published":"2004","updated_at":"2026-07-22T22:21:47Z","subjects":["Mechanical Engineering."],"languages":["eng"],"rights":["M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission."],"rights_urls":["http://dspace.mit.edu/handle/1721.1/7582"],"identifier_entries":[]},"links":{"outbound_url":"http://hdl.handle.net/1721.1/30334","outbound_label":"Handle","outbound_source":"dc:identifier.uri"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.advisor","label":"Advisor","values":["Leslie K. Norford."]},{"key":"dc:contributor.department","label":"Department","values":["Massachusetts Institute of Technology. Dept. of Mechanical Engineering."]},{"key":"dc:contributor.other","label":"Dc Contributor Other","values":["Massachusetts Institute of Technology. Dept. of Mechanical Engineering."]},{"key":"dc:creator","label":"Author","values":["Spindler, Henry C. (Henry Carlton), 1970-"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2006-03-24T18:41:16Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2006-03-24T18:41:16Z"]},{"key":"dc:date.issued","label":"Date","values":["2004"]},{"key":"dc:publisher","label":"Institution","values":["Massachusetts Institute of Technology"]},{"key":"dc:type","label":"Dc Type","values":["Thesis"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Mechanical Engineering."]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language.iso","label":"Language (ISO)","values":["eng"]},{"key":"dc:rights","label":"Dc Rights","values":["M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission."]},{"key":"dc:rights.uri","label":"Rights URI","values":["http://dspace.mit.edu/handle/1721.1/7582"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/1721.1/30334"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description","label":"Description","values":["Thesis (Ph. D.)--Massachusetts Institute of Technology, Dept. of Mechanical Engineering, 2004.","\"September 2004.\"","Includes bibliographical references (p. 285-294)."]},{"key":"dc:description.abstract","label":"Abstract","values":["The majority of commercial buildings today are designed to be mechanically cooled. To make the task of air conditioning buildings simpler, and in some cases more energy efficient, windows are sealed shut, eliminating occupants' direct access to fresh air. Implementation of an alternative cooling strategy-mixed-mode cooling-is demonstrated in this thesis to yield substantial savings in cooling energy consumption in many U.S. locations. A mixed-mode cooling strategy is one that relies on several different means of delivering cooling to the occupied space. These different means, or modes, of cooling could include: different forms of natural ventilation through operable windows, ventilation assisted by low-power fans, and mechanical air conditioning. Three significant contributions are presented in this thesis. A flexible system identification framework was developed that is well-suited to accommodate the unique features of mixed-mode buildings. Further, the effectiveness of this framework was demonstrated on an actual multi- zone, mixed-mode building, with model prediction accuracy shown to exceed that published for other naturally ventilated or mixed-mode buildings, none of which exhibited the complexity of this building. Finally, an efficient algorithm was constructed to optimize control strategies over extended planning horizons using a model-based approach. The algorithm minimizes energy consumption subject to the constraint that indoor temperatures satisfy comfort requirements. The system identification framework was applied to another mixed-mode building, where it was found that the aspects integral to the modeling framework led to prediction improvements relative to a simple model.","(cont.) Lack of data regarding building apertures precluded the use of the model for control purposes. An additional contribution was the development of a procedure for extracting building time constants from experimental data in such a way that they are constrained to be physically meaningful."]},{"key":"dc:description.degree","label":"Dc Description Degree","values":["Ph.D."]},{"key":"dc:format.mimetype","label":"Dc Format Mimetype","values":["application/pdf"]},{"key":"dc:title","label":"Title","values":["System identification and optimal control for mixed-mode cooling"]}]}],"canonical_facts":{"dc:contributor.advisor":["Leslie K. Norford."],"dc:contributor.department":["Massachusetts Institute of Technology. Dept. of Mechanical Engineering."],"dc:contributor.other":["Massachusetts Institute of Technology. Dept. of Mechanical Engineering."],"dc:creator":["Spindler, Henry C. (Henry Carlton), 1970-"],"dc:date.accessioned":["2006-03-24T18:41:16Z"],"dc:date.available":["2006-03-24T18:41:16Z"],"dc:date.issued":["2004"],"dc:description":["Thesis (Ph. D.)--Massachusetts Institute of Technology, Dept. of Mechanical Engineering, 2004.","\"September 2004.\"","Includes bibliographical references (p. 285-294)."],"dc:description.abstract":["The majority of commercial buildings today are designed to be mechanically cooled. To make the task of air conditioning buildings simpler, and in some cases more energy efficient, windows are sealed shut, eliminating occupants' direct access to fresh air. Implementation of an alternative cooling strategy-mixed-mode cooling-is demonstrated in this thesis to yield substantial savings in cooling energy consumption in many U.S. locations. A mixed-mode cooling strategy is one that relies on several different means of delivering cooling to the occupied space. These different means, or modes, of cooling could include: different forms of natural ventilation through operable windows, ventilation assisted by low-power fans, and mechanical air conditioning. Three significant contributions are presented in this thesis. A flexible system identification framework was developed that is well-suited to accommodate the unique features of mixed-mode buildings. Further, the effectiveness of this framework was demonstrated on an actual multi- zone, mixed-mode building, with model prediction accuracy shown to exceed that published for other naturally ventilated or mixed-mode buildings, none of which exhibited the complexity of this building. Finally, an efficient algorithm was constructed to optimize control strategies over extended planning horizons using a model-based approach. The algorithm minimizes energy consumption subject to the constraint that indoor temperatures satisfy comfort requirements. The system identification framework was applied to another mixed-mode building, where it was found that the aspects integral to the modeling framework led to prediction improvements relative to a simple model.","(cont.) Lack of data regarding building apertures precluded the use of the model for control purposes. An additional contribution was the development of a procedure for extracting building time constants from experimental data in such a way that they are constrained to be physically meaningful."],"dc:description.degree":["Ph.D."],"dc:format.mimetype":["application/pdf"],"dc:identifier.uri":["http://hdl.handle.net/1721.1/30334"],"dc:language.iso":["eng"],"dc:publisher":["Massachusetts Institute of Technology"],"dc:rights":["M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission."],"dc:rights.uri":["http://dspace.mit.edu/handle/1721.1/7582"],"dc:subject":["Mechanical Engineering."],"dc:title":["System identification and optimal control for mixed-mode cooling"],"dc:type":["Thesis"]},"updated_at":"2026-07-22T22:21:47Z"}