Back to results

Victoria University of Technology

Fault location on EHV lines using wideband spread spectrum techniques

Abstract

dc:description.abstract

Electrical authorities require fast and accurate fault locators to protect tha quality of supply and reduce outage times. Spread spectrum techniques perform well in high noise environments such as power lines and their use in radar ranging is well known. Existing power line carrier (PLC) equipment may be used to transmit a direct sequence signal down a faulted EHV line. The fault position may then be calculated from correlation analysis of the reflected waveforms. In this thesis the fault location process has been simulated on a digital computer taking into account the frequency variation of the PLC interface and line parameters over the spread spectrum bandwidth. The effect of waveform characteristics, fault location and resistance are examined for a 100 km double transposed line with a single phase to ground fault.

Degree

thesis:*
Name dc:type.qualificationname
phd
Level dc:type.qualificationlevel
doctoral
Grantor dc:publisher.institution
Victoria University of Technology
Year dc:date.issued
1999

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Taylor, Victor

Subjects

dc:subject × 2

Rights

Language dc:language
en

Chain of custody

source
Harvested from
Victoria University (Australia)
Base URL
vuir.vu.edu.au/cgi/oai2
Last updated
2026-07-24
Source record
OAI-PMH GetRecord
citation

Taylor, Victor. Fault location on EHV lines using wideband spread spectrum techniques. doctoral thesis, Victoria University of Technology, 1999.