On-line Calibration of Instrument Transformers Using Synchrophasor Measurements

Abstract

dc:description.abstract

The world of power systems is ever changing; ever evolving. One such evolution was the advent of Phasor Measurement Units (PMUs). With the introduction of PMUs in the field, power system monitoring and control changed for the better. Innovative and efficient algorithms that used synchrophasors came to be written. To make these algorithms robust, it became necessary to remove errors that crept into the power system with time and usage. Thus the process of calibration became essential when practical decisions started being made based on PMU measurements. In the context of this thesis ‘calibration’ is the method used to estimate a correction factor which, when multiplied with the respective measurement, negates the effect of any errors that might have crept into them due to the instrument transformers located at the inputs of a PMU or the PMU device itself. Though this thesis mainly deals with the calibration of instrument transformers, work has been done previously for calibrating other components of a power system. A brief description of those methods have been provided along with a history on instrument transformer calibration. Three new methodologies for instrument transformer calibration have been discussed in details in this thesis. The first method describes how only voltage transformers can be calibrated by placing optimal number of good quality voltage measurements at strategic locations in the grid, in presence of ratio errors in the instrument transformers and Gaussian errors in the PMUs. The second method provides a way to calibrate all instrument transformers (both current and voltage) in presence of only one good quality voltage measurement located at the end of a tie-line. This method assumes that all the instrument transformers have ratio errors and the PMUs have quantization errors. The third method attains the same objective as the second one, with the additional constraint that the data obtained from the field may be contaminated. Thus, the third method shows how calibration of all the instrument transformers can be done with data that is intermittent and is therefore, the most practical approach (of the three) for instrument transformer calibration.

Degree

thesis:*
Name thesis:degree_name
Master of Science
Level thesis:degree_level
masters
Discipline thesis:degree_discipline
Electrical Engineering
Department dc:contributor.department
Electrical Engineering
Grantor dc:publisher
Virginia Tech
Year dc:date.issued
2017

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Chatterjee, Paroma
Chair dc:contributor.committeechair
  • De La Ree, Jaime
Committee members dc:contributor.committeemember
  • Thorp, James S.
  • Centeno, Virgilio A.

Subjects

dc:subject × 6

Rights

dc:rights
Statement dc:rights
  • In Copyright
Language dc:language.iso
en_US

Identifiers

dc:identifier.*
Dc Identifier Other
etd-12212015-174949
OAI identifier oai:identifier
oai:vtechworks.lib.vt.edu:10919/79857

Chain of custody

source
Harvested from
Virginia Tech
Base URL
vtechworks.lib.vt.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Chatterjee, Paroma. On-line Calibration of Instrument Transformers Using Synchrophasor Measurements. masters thesis, Virginia Tech, 2017. http://hdl.handle.net/10919/79857