Back to results

Virginia Tech

On-Line Transient Stability Analysis of a Multi-Machine Power System Using the Energy Approach

Abstract

dc:description.abstract

This thesis investigates and develops a direct method for transient stability analysis using the energy approach [1] and the Phasor Measurement Units (PMUs). The originality of this new method results from a combination of a prediction of the post-fault trajectory based on the PMUs and the Transient Energy Function of a multimachine system. Thanks to the PMUs, the weakness of the direct methods, which is the over-simplification of the generator model, is overcome. This new method consists of fitting a curve to the data of the post-fault path provided by PMUs and identifying the controlling unstable equilibrium point (c.u.e.p.). Two second-order linear models have been estimated and evaluated from a prediction viewpoint. These are a polynomial function and an auto-regressive model. These parameters have been estimated by means of the least-squares estimator. They have been compared to the model proposed by Y. Ohura et al. [6], which has been upgraded into an iterative algorithm. The post-fault trajectory is predicted until the exit point located on the Potential Energy Boundary Surface (p.e.b.s.) is reached. In order to detect with efficiency this exit point and to find the c.u.e.p., it is proposed a combination of the so called "Ball-Drop" method [22] and an improved version of the Shadowing method. These combined procedures give accurate results when they are compared to the step-by-step method, which directly integrates the differential equations using a fourth-order Runga-Kutta method. The simulations have been carried out on a 3-machine system and on the 10-machine New-England power system.

Degree

thesis:*
Name thesis:degree_name
Master of Science
Level thesis:degree_level
masters
Discipline thesis:degree_discipline
Electrical Engineering
Department dc:contributor.department
Electrical Engineering
Grantor dc:publisher
Virginia Tech
Year dc:date.issued
1997

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Vidalinc, Antoine
Chair dc:contributor.committeechair
  • Mili, Lamine M.
Committee members dc:contributor.committeemember
  • Phadke, Arun G.
  • Liu, Yilu

Subjects

dc:subject × 5

Rights

dc:rights
Statement dc:rights
  • In Copyright

Identifiers

dc:identifier.*
Dc Identifier Other
etd-61797-12279
OAI identifier oai:identifier
oai:vtechworks.lib.vt.edu:10919/36842

Chain of custody

source
Harvested from
Virginia Tech
Base URL
vtechworks.lib.vt.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Vidalinc, Antoine. On-Line Transient Stability Analysis of a Multi-Machine Power System Using the Energy Approach. masters thesis, Virginia Tech, 1997. http://hdl.handle.net/10919/36842