{"id":{"repo_id":"vt","oai_identifier":"oai:vtechworks.lib.vt.edu:10919/27241"},"canonical_url":"https://search.dev.ndltd.org/etd/vt/oai:vtechworks.lib.vt.edu:10919/27241","repository":{"repo_id":"vt","name":"Virginia Tech","base_url":"https://vtechworks.lib.vt.edu/oai/request"},"display":{"title":"Non-Invasive Permeability Assessment of High-Performance Concrete Bridge Deck Mixtures","abstract":"Concrete construction methods and practices influence the final in-place quality of concrete. A low permeability concrete mixture does not alone ensure quality in-place concrete. If the concrete mixture is not transported, placed and cured properly, it may not exhibit the desired durability and mechanical properties. This study investigates the in-place permeation properties of low permeability concrete bridge decks mixtures used in the Commonwealth of Virginia. Permeation properties were assessed in both the laboratory and in the field using 4-point Wenner array electrical resistivity, surface air flow (SAF), and chloride ion penetrability (ASTM C 1202-97). Laboratory test specimens consisted of two concrete slabs having dimensions of 280 x 280 x 102-mm (11 x 11 x 4-in) and twelve 102 x 204-mm (4 x 8-in) cylinders per concrete mixture. Specimens were tested at 7, 28 and 91-days. Thirteen cylinder specimens per concrete mixture underwent standard curing in a saturated limewater bath. The simulated field-curing regimes used wet burlap and plastic sheeting for 3 (3B) and 7 days (7B) respectively and was applied to both slabs and cylinder specimens. Slab specimen were tested on finished surface using the SAF at 28 and 91 days, and 4-point electrical resistivity measurements at 1, 3, 7, 14, 28 and 91 days. Compressive strength (CS) tests were conducted at 7 and 28 days. Chloride ion penetrability tests were performed at 7, 28, and 91 days. Statistical analyses were performed to assess the significance of the relationships for the following: Total charge passed and initial current (ASTM C 1202-97); 3B resistivity and 7B resistivity; Slab and cylinder resistivity; Slab resistivity and ASTM C-1202-97 (Total Charge and Initial current); and Surface Air Flow and ASTM C-1202-97. Field cast specimens, test slabs and cylinders, were cast on-site during concrete bridge deck construction. The slab dimensions were 30.5 x 40.6 x 10.2-cm (12 x 16 x 4 in.), and the cylinders were 10.2 x 20.4-cm (4 x 8-in). In-situ SAF and resistivity measurements were taken on the bridge deck at 14, 42 and 91 days. In-place SAF and resistivity measurements on laboratory field cast slabs were taken at 7, 14 and 28-days. ASTM C 1202-97 specimens were prepared from field cast cylinders and tested at 7 and 28 and 42-days. The relationship between in-place permeation measures from field specimens was compared to laboratory data. Results indicated no difference in chloride ion penetrability (Figures 7.4 and 7.5) and 28-day compressive strength (Figure 7.2) with regard to differing simulated field curing regimes, for same age testing. There was no significant difference at the 95 % confidence level between 3B resistivity and 7B resistivity specimens tested at the same age (Figures 7.9 and 7.10). A well defined relationship was observed between total charge passed and initial current (Figure 7-6). An inverse power function was found to describe the relationship between charge passed/initial current and electrical resistivity for all laboratory mixtures used in this study (Figure 7.17 – 7.22). Field data was used to validate laboratory established models for charge passed/initial current and electrical resistivity. Laboratory established models were able to predict 30 to 50% of the field data (Figures 7.31 – 7.34). Results indicate that the SAF lacked the sensitivity to classify the range of concretes used in this study (Figure 7.24).","abstract_html":"Concrete construction methods and practices influence the final in-place quality of concrete. A low permeability concrete mixture does not alone ensure quality in-place concrete. If the concrete mixture is not transported, placed and cured properly, it may not exhibit the desired durability and mechanical properties. This study investigates the in-place permeation properties of low permeability concrete bridge decks mixtures used in the Commonwealth of Virginia. Permeation properties were assessed in both the laboratory and in the field using 4-point Wenner array electrical resistivity, surface air flow (SAF), and chloride ion penetrability (ASTM C 1202-97). Laboratory test specimens consisted of two concrete slabs having dimensions of 280 x 280 x 102-mm (11 x 11 x 4-in) and twelve 102 x 204-mm (4 x 8-in) cylinders per concrete mixture. Specimens were tested at 7, 28 and 91-days. Thirteen cylinder specimens per concrete mixture underwent standard curing in a saturated limewater bath. The simulated field-curing regimes used wet burlap and plastic sheeting for 3 (3B) and 7 days (7B) respectively and was applied to both slabs and cylinder specimens. Slab specimen were tested on finished surface using the SAF at 28 and 91 days, and 4-point electrical resistivity measurements at 1, 3, 7, 14, 28 and 91 days. Compressive strength (CS) tests were conducted at 7 and 28 days. Chloride ion penetrability tests were performed at 7, 28, and 91 days. Statistical analyses were performed to assess the significance of the relationships for the following: Total charge passed and initial current (ASTM C 1202-97); 3B resistivity and 7B resistivity; Slab and cylinder resistivity; Slab resistivity and ASTM C-1202-97 (Total Charge and Initial current); and Surface Air Flow and ASTM C-1202-97. Field cast specimens, test slabs and cylinders, were cast on-site during concrete bridge deck construction. The slab dimensions were 30.5 x 40.6 x 10.2-cm (12 x 16 x 4 in.), and the cylinders were 10.2 x 20.4-cm (4 x 8-in). In-situ SAF and resistivity measurements were taken on the bridge deck at 14, 42 and 91 days. In-place SAF and resistivity measurements on laboratory field cast slabs were taken at 7, 14 and 28-days. ASTM C 1202-97 specimens were prepared from field cast cylinders and tested at 7 and 28 and 42-days. The relationship between in-place permeation measures from field specimens was compared to laboratory data. Results indicated no difference in chloride ion penetrability (Figures 7.4 and 7.5) and 28-day compressive strength (Figure 7.2) with regard to differing simulated field curing regimes, for same age testing. There was no significant difference at the 95 % confidence level between 3B resistivity and 7B resistivity specimens tested at the same age (Figures 7.9 and 7.10). A well defined relationship was observed between total charge passed and initial current (Figure 7-6). An inverse power function was found to describe the relationship between charge passed/initial current and electrical resistivity for all laboratory mixtures used in this study (Figure 7.17 – 7.22). Field data was used to validate laboratory established models for charge passed/initial current and electrical resistivity. Laboratory established models were able to predict 30 to 50% of the field data (Figures 7.31 – 7.34). Results indicate that the SAF lacked the sensitivity to classify the range of concretes used in this study (Figure 7.24).","abstract_has_math":false,"creators":["Bryant, James William Jr."],"institution":"Virginia Tech","degree_name":"Ph. D.","degree_level":"doctoral","degree_discipline":"Civil Engineering","degree_department":"Civil Engineering","school":null,"contributors":[],"advisors":[],"committee_chairs":["de la Garza, Jesus M.","Weyers, Richard E."],"committee_members":["Lefter, James","Reynolds, William T. Jr.","Barker, Richard M."],"year":2001,"date_issued":"2001-04-19","date_published":"2001-04-19","updated_at":"2026-07-22T22:20:21Z","subjects":["Permeability","Chloride Ion Penetrability","High-Performance Concrete","Concrete Resistivity","Initial current","Nondestructive Testing"],"languages":[],"rights":["In Copyright"],"rights_urls":["http://rightsstatements.org/vocab/InC/1.0/"],"identifier_entries":[{"key":"dc:identifier.other","label":"Dc Identifier Other","values":["etd-04252001-230753"],"render_values":[{"text":"etd-04252001-230753","href":null,"code":true}]}]},"links":{"outbound_url":"http://hdl.handle.net/10919/27241","outbound_label":"Handle","outbound_source":"dc:identifier.uri"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor.committeechair","label":"Committee Chair","values":["de la Garza, Jesus M.","Weyers, Richard E."]},{"key":"dc:contributor.committeemember","label":"Committee Member","values":["Lefter, James","Reynolds, William T. Jr.","Barker, Richard M."]},{"key":"dc:contributor.department","label":"Department","values":["Civil Engineering"]},{"key":"dc:creator","label":"Author","values":["Bryant, James William Jr."]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date.accessioned","label":"Dc Date Accessioned","values":["2014-03-14T20:10:43Z"]},{"key":"dc:date.available","label":"Dc Date Available","values":["2014-03-14T20:10:43Z","2002-04-27"]},{"key":"dc:date.issued","label":"Date","values":["2001-04-19"]},{"key":"dc:publisher","label":"Institution","values":["Virginia Tech"]},{"key":"dc:type","label":"Dc Type","values":["Dissertation"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Civil Engineering"]},{"key":"thesis:degree_level","label":"Degree Level","values":["doctoral"]},{"key":"thesis:degree_name","label":"Degree Name","values":["Ph. D."]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["Virginia Polytechnic Institute and State University"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Permeability","Chloride Ion Penetrability","High-Performance Concrete","Concrete Resistivity","Initial current","Nondestructive Testing"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:rights","label":"Dc Rights","values":["In Copyright"]},{"key":"dc:rights.uri","label":"Rights URI","values":["http://rightsstatements.org/vocab/InC/1.0/"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier.other","label":"Dc Identifier Other","values":["etd-04252001-230753"]},{"key":"dc:identifier.uri","label":"Identifier URI","values":["http://hdl.handle.net/10919/27241"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description.abstract","label":"Abstract","values":["Concrete construction methods and practices influence the final in-place quality of concrete. A low permeability concrete mixture does not alone ensure quality in-place concrete. If the concrete mixture is not transported, placed and cured properly, it may not exhibit the desired durability and mechanical properties. This study investigates the in-place permeation properties of low permeability concrete bridge decks mixtures used in the Commonwealth of Virginia. Permeation properties were assessed in both the laboratory and in the field using 4-point Wenner array electrical resistivity, surface air flow (SAF), and chloride ion penetrability (ASTM C 1202-97). Laboratory test specimens consisted of two concrete slabs having dimensions of 280 x 280 x 102-mm (11 x 11 x 4-in) and twelve 102 x 204-mm (4 x 8-in) cylinders per concrete mixture. Specimens were tested at 7, 28 and 91-days. Thirteen cylinder specimens per concrete mixture underwent standard curing in a saturated limewater bath. The simulated field-curing regimes used wet burlap and plastic sheeting for 3 (3B) and 7 days (7B) respectively and was applied to both slabs and cylinder specimens. Slab specimen were tested on finished surface using the SAF at 28 and 91 days, and 4-point electrical resistivity measurements at 1, 3, 7, 14, 28 and 91 days. Compressive strength (CS) tests were conducted at 7 and 28 days. Chloride ion penetrability tests were performed at 7, 28, and 91 days. Statistical analyses were performed to assess the significance of the relationships for the following: Total charge passed and initial current (ASTM C 1202-97); 3B resistivity and 7B resistivity; Slab and cylinder resistivity; Slab resistivity and ASTM C-1202-97 (Total Charge and Initial current); and Surface Air Flow and ASTM C-1202-97. Field cast specimens, test slabs and cylinders, were cast on-site during concrete bridge deck construction. The slab dimensions were 30.5 x 40.6 x 10.2-cm (12 x 16 x 4 in.), and the cylinders were 10.2 x 20.4-cm (4 x 8-in). In-situ SAF and resistivity measurements were taken on the bridge deck at 14, 42 and 91 days. In-place SAF and resistivity measurements on laboratory field cast slabs were taken at 7, 14 and 28-days. ASTM C 1202-97 specimens were prepared from field cast cylinders and tested at 7 and 28 and 42-days. The relationship between in-place permeation measures from field specimens was compared to laboratory data. Results indicated no difference in chloride ion penetrability (Figures 7.4 and 7.5) and 28-day compressive strength (Figure 7.2) with regard to differing simulated field curing regimes, for same age testing. There was no significant difference at the 95 % confidence level between 3B resistivity and 7B resistivity specimens tested at the same age (Figures 7.9 and 7.10). A well defined relationship was observed between total charge passed and initial current (Figure 7-6). An inverse power function was found to describe the relationship between charge passed/initial current and electrical resistivity for all laboratory mixtures used in this study (Figure 7.17 – 7.22). Field data was used to validate laboratory established models for charge passed/initial current and electrical resistivity. Laboratory established models were able to predict 30 to 50% of the field data (Figures 7.31 – 7.34). Results indicate that the SAF lacked the sensitivity to classify the range of concretes used in this study (Figure 7.24)."]},{"key":"dc:description.degree","label":"Dc Description Degree","values":["Ph. D."]},{"key":"dc:title","label":"Title","values":["Non-Invasive Permeability Assessment of High-Performance Concrete Bridge Deck Mixtures"]}]}],"canonical_facts":{"dc:contributor.committeechair":["de la Garza, Jesus M.","Weyers, Richard E."],"dc:contributor.committeemember":["Lefter, James","Reynolds, William T. Jr.","Barker, Richard M."],"dc:contributor.department":["Civil Engineering"],"dc:creator":["Bryant, James William Jr."],"dc:date.accessioned":["2014-03-14T20:10:43Z"],"dc:date.available":["2014-03-14T20:10:43Z","2002-04-27"],"dc:date.issued":["2001-04-19"],"dc:description.abstract":["Concrete construction methods and practices influence the final in-place quality of concrete. A low permeability concrete mixture does not alone ensure quality in-place concrete. If the concrete mixture is not transported, placed and cured properly, it may not exhibit the desired durability and mechanical properties. This study investigates the in-place permeation properties of low permeability concrete bridge decks mixtures used in the Commonwealth of Virginia. Permeation properties were assessed in both the laboratory and in the field using 4-point Wenner array electrical resistivity, surface air flow (SAF), and chloride ion penetrability (ASTM C 1202-97). Laboratory test specimens consisted of two concrete slabs having dimensions of 280 x 280 x 102-mm (11 x 11 x 4-in) and twelve 102 x 204-mm (4 x 8-in) cylinders per concrete mixture. Specimens were tested at 7, 28 and 91-days. Thirteen cylinder specimens per concrete mixture underwent standard curing in a saturated limewater bath. The simulated field-curing regimes used wet burlap and plastic sheeting for 3 (3B) and 7 days (7B) respectively and was applied to both slabs and cylinder specimens. Slab specimen were tested on finished surface using the SAF at 28 and 91 days, and 4-point electrical resistivity measurements at 1, 3, 7, 14, 28 and 91 days. Compressive strength (CS) tests were conducted at 7 and 28 days. Chloride ion penetrability tests were performed at 7, 28, and 91 days. Statistical analyses were performed to assess the significance of the relationships for the following: Total charge passed and initial current (ASTM C 1202-97); 3B resistivity and 7B resistivity; Slab and cylinder resistivity; Slab resistivity and ASTM C-1202-97 (Total Charge and Initial current); and Surface Air Flow and ASTM C-1202-97. Field cast specimens, test slabs and cylinders, were cast on-site during concrete bridge deck construction. The slab dimensions were 30.5 x 40.6 x 10.2-cm (12 x 16 x 4 in.), and the cylinders were 10.2 x 20.4-cm (4 x 8-in). In-situ SAF and resistivity measurements were taken on the bridge deck at 14, 42 and 91 days. In-place SAF and resistivity measurements on laboratory field cast slabs were taken at 7, 14 and 28-days. ASTM C 1202-97 specimens were prepared from field cast cylinders and tested at 7 and 28 and 42-days. The relationship between in-place permeation measures from field specimens was compared to laboratory data. Results indicated no difference in chloride ion penetrability (Figures 7.4 and 7.5) and 28-day compressive strength (Figure 7.2) with regard to differing simulated field curing regimes, for same age testing. There was no significant difference at the 95 % confidence level between 3B resistivity and 7B resistivity specimens tested at the same age (Figures 7.9 and 7.10). A well defined relationship was observed between total charge passed and initial current (Figure 7-6). An inverse power function was found to describe the relationship between charge passed/initial current and electrical resistivity for all laboratory mixtures used in this study (Figure 7.17 – 7.22). Field data was used to validate laboratory established models for charge passed/initial current and electrical resistivity. Laboratory established models were able to predict 30 to 50% of the field data (Figures 7.31 – 7.34). Results indicate that the SAF lacked the sensitivity to classify the range of concretes used in this study (Figure 7.24)."],"dc:description.degree":["Ph. D."],"dc:identifier.other":["etd-04252001-230753"],"dc:identifier.uri":["http://hdl.handle.net/10919/27241"],"dc:publisher":["Virginia Tech"],"dc:rights":["In Copyright"],"dc:rights.uri":["http://rightsstatements.org/vocab/InC/1.0/"],"dc:subject":["Permeability","Chloride Ion Penetrability","High-Performance Concrete","Concrete Resistivity","Initial current","Nondestructive Testing"],"dc:title":["Non-Invasive Permeability Assessment of High-Performance Concrete Bridge Deck Mixtures"],"dc:type":["Dissertation"],"thesis:degree_discipline":["Civil Engineering"],"thesis:degree_level":["doctoral"],"thesis:degree_name":["Ph. D."],"thesis:institution_name":["Virginia Polytechnic Institute and State University"]},"updated_at":"2026-07-22T22:20:21Z"}