Back to results

Virginia Tech

Modern Adaptive Protection and Control Techniques for Enhancing Distribution Grid Resiliency

Abstract

dc:description.abstract

Power distribution systems have underwent a lot of significant changes in the last two decades. Wide-scale integration of Distributed Energy Resources (DERs) have made the distribution grid more resilient to abnormal conditions and severe weather induced outages. These DERs enhance the reliability of the system to bounce back from an abnormal situation rather quickly. However, the conventional notion of a radial system with unidirectional power flow does not hold true due to the addition of these DERs. Bidirectional power flow has challenged the conventional protection schemes in place. The most notable effects on the protection schemes can be seen in the field of islanding or Loss of Mains(LOM) detection and general fault identification and isolation. Adaptive protection schemes are needed to properly resolve these issues. Although, previous works in this field have dealt with this situation, a more comprehensive approach needs to be taken considering multiple topologies for developing adaptive protection schemes. The most common protective devices widely deployed in the distribution system such as overcurrent relays, reverse power relays at Point of Common Coupling(PCC), fuses, reclosers and feeder breakers need to studied in implementing these schemes. The work presented in this dissertation deals with simulation based and analytical approaches to tackle the issues of islanding and adaptive protection schemes. First we propose a multiprinciple passive islanding detection technique which relies on local PCC measurements, thus reducing the need of additional infrastructure and still ensuring limited Non Detection Zone (NDZ). The next step to islanding detection would be to sustain a islanded distribution system in order to reduce the restoration time and still supply power to critical loads. Such an approach to maintain generator load balance upon islanding detection is studied next by appropriate shedding of non-critical and low priority critical loads based upon voltage sensitivity analysis. Thereafter, adaptive protection schemes considering limited communication dependency is studied with properly assigning relay settings in directional overcurrent relays (DOCRs), which are one of the most widely deployed protective devices in distribution systems by catering to multiple topologies and contingencies. A simulation based technique is discussed first and then an analytical approach to solve the conventional optimal relay coordination problem using Mixed Integer Linear Programming (MILP) with the usage of multiple setting groups is studied. All these approaches make the distribution more robust and resilient to system faults and ensure proper fault identification and isolation, ensuring overall safety of system.

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy
Level thesis:degree_level
doctoral
Discipline thesis:degree_discipline
Electrical Engineering
Department dc:contributor.department
Electrical Engineering
Grantor dc:publisher
Virginia Tech
Year dc:date.issued
2021

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Barik, Tapas Kumar
Chair dc:contributor.committeechair
  • Centeno, Virgilio A.
Committee members dc:contributor.committeemember
  • Southward, Steve C.
  • De La Ree, Jaime
  • Baumann, William T.
  • Liu, Chen-Ching

Subjects

dc:subject × 8

Rights

dc:rights
Statement dc:rights
  • In Copyright

Identifiers

dc:identifier.*
Dc Identifier Other
vt_gsexam:31231
OAI identifier oai:identifier
oai:vtechworks.lib.vt.edu:10919/103644

Chain of custody

source
Harvested from
Virginia Tech
Base URL
vtechworks.lib.vt.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Barik, Tapas Kumar. Modern Adaptive Protection and Control Techniques for Enhancing Distribution Grid Resiliency. doctoral thesis, Virginia Tech, 2021. http://hdl.handle.net/10919/103644