Abstract
dc:description.abstractTwo different iron oxide nanofluids were tested for heat transfer properties in industrial cooling systems. The nanofluids either had 30 nm particles with a wide size distribution to include particles greater than 1 micrometer or 15 nm particles with greater than 95% of the particles less than 33 nm. Calorimetry and thermal circuit modeling indicate that the 15 nm particle ferrofluid enhanced heat capacity. The smaller particle ferrofluid also demonstrated up to a 39% improvement in heat transfer, while the larger particle ferrofluid degraded the heat transfer performance. Particles from the larger particle ferrofluid were noted as settling out of a circulating system and therefore not participating in the bulk fluid properties. Application of 0.32% 15nm particles in an open cooling system improved cooling tower efficiency by 7.7% at a flow rate of 11.4 liter per minute and improved cooling tower efficiency by 3.3% at a flow rate of 22.7 liter per minute, while applying 0.53% 15 nm particles also improved cooling tower efficiency but was less effective than the lower concentration.
Degree
thesis:*- Name thesis:degree_name
- Master of Science
- Level thesis:degree_level
- Thesis
- Discipline thesis:degree_discipline
- Chemistry
- Year dc:date.available
- 2012
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Stuart, Dale
- Contributors dc:contributor
-
- Everett Carpenter
- Maryanne Collinson
- Frank Gupton
- Hani El-Kaderi
Subjects
dc:subject × 7Rights
dc:rights- Statement dc:rights
-
- © The Author
Identifiers
dc:identifier.*- Identifier
- https://scholarscompass.vcu.edu/etd/425
- OAI identifier oai:identifier
- oai:scholarscompass.vcu.edu:etd-1424