Development of a test facility for making in-duct sound measurements according to Astm E477-1984
Abstract
dc:description.abstractDuct silencers must reduce sound levels enough to be noticed by the human ear. By placing the appropriate duct silencer in the air-conditioning duct system, sound levels in rooms where noise is a problem can be significantly reduced. Only through insertion loss measurements can the appropriate silencer be determined for the desired noise reduction; This thesis involves the modification and qualification of the reverberation chamber in the Multi-Function Lab at the University of Nevada, Las Vegas, for the purpose of creating a controlled sound testing environment. It also involves the design and construction of facilities for making insertion loss measurements. The thesis concludes with the testing and analysis of five duct silencers. (Abstract shortened with permission of author.).