{"id":{"repo_id":"uiuc","oai_identifier":"oai:www.ideals.illinois.edu:2142/49599"},"canonical_url":"https://search.dev.ndltd.org/etd/uiuc/oai:www.ideals.illinois.edu:2142/49599","repository":{"repo_id":"uiuc","name":"University of Illinois - Urbana-Champaign","base_url":"https://www.ideals.illinois.edu/oai-pmh"},"display":{"title":"Distribution system analysis using local-area voltage measurements","abstract":"\"The move toward a \"\"smarter\"\" electric grid, along with increased renewable penetration, has motivated the need for increased power system visibility. This is due to the fact that these energy sources introduce transients that previously were not as common or pronounced within the distribution system. Increased distribution system observability can be realized with the implementation of Phasor Measurement Units (PMUs), which measure the AC voltage and current traveling throughout the grid. However, questions related to both the economic investment and the actionable informational gains are the biggest impediments to the installation of more PMUs within the distribution system. A relatively low-cost alternative to many of the commercially available PMUs is the Frequency Disturbance Recorder (FDR), which measures voltage at the 120 V-outlet level. This research proposes using the voltage information obtained from FDRs to validate the benefits of installing PMUs at the distribution level; the work has looked into what system events, both transmission and distribution, can be seen at the distribution level. The thesis begins by providing a background on the state of the distribution system and the effects of new grid technologies. Afterward, the FDR will be introduced, and an example of the information that can be obtained from the data will be shown.\"","abstract_html":"&quot;The move toward a &quot;&quot;smarter&quot;&quot; electric grid, along with increased renewable penetration, has motivated the need for increased power system visibility. This is due to the fact that these energy sources introduce transients that previously were not as common or pronounced within the distribution system. Increased distribution system observability can be realized with the implementation of Phasor Measurement Units (PMUs), which measure the AC voltage and current traveling throughout the grid. However, questions related to both the economic investment and the actionable informational gains are the biggest impediments to the installation of more PMUs within the distribution system. A relatively low-cost alternative to many of the commercially available PMUs is the Frequency Disturbance Recorder (FDR), which measures voltage at the 120 V-outlet level. This research proposes using the voltage information obtained from FDRs to validate the benefits of installing PMUs at the distribution level; the work has looked into what system events, both transmission and distribution, can be seen at the distribution level. The thesis begins by providing a background on the state of the distribution system and the effects of new grid technologies. Afterward, the FDR will be introduced, and an example of the information that can be obtained from the data will be shown.&quot;","abstract_has_math":false,"creators":["Phillips, Desiree"],"institution":"University of Illinois at Urbana-Champaign","degree_name":"M.S.","degree_level":"Thesis","degree_discipline":"Electrical & Computer Engr","degree_department":null,"school":null,"contributors":["Overbye, Thomas J."],"advisors":[],"committee_chairs":[],"committee_members":[],"year":2014,"date_issued":"2014-05-30T16:51:49Z","date_published":"2014-05-30T16:51:49Z","updated_at":"2026-07-22T22:25:38Z","subjects":["Electric Power System","Distribution System","Distributed Voltage Measurement Unit","Frequency Disturbance Recorder"],"languages":["en"],"rights":["Copyright 2014 Desiree Phillips"],"rights_urls":[],"identifier_entries":[]},"links":{"outbound_url":"http://hdl.handle.net/2142/49599","outbound_label":"Handle","outbound_source":"dc:identifier"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor","label":"Contributor","values":["Overbye, Thomas J."]},{"key":"dc:creator","label":"Author","values":["Phillips, Desiree"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date","label":"Dc Date","values":["2014-05-30T16:51:49Z","2014-05"]},{"key":"dc:type","label":"Dc Type","values":["text"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Electrical & Computer Engr"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Thesis"]},{"key":"thesis:degree_name","label":"Degree Name","values":["M.S."]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["University of Illinois at Urbana-Champaign"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["Electric Power System","Distribution System","Distributed Voltage Measurement Unit","Frequency Disturbance Recorder"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language","label":"Dc Language","values":["en"]},{"key":"dc:rights","label":"Dc Rights","values":["Copyright 2014 Desiree Phillips"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["http://hdl.handle.net/2142/49599"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description","label":"Description","values":["\"The move toward a \"\"smarter\"\" electric grid, along with increased renewable penetration, has motivated the need for increased power system visibility. This is due to the fact that these energy sources introduce transients that previously were not as common or pronounced within the distribution system. Increased distribution system observability can be realized with the implementation of Phasor Measurement Units (PMUs), which measure the AC voltage and current traveling throughout the grid. However, questions related to both the economic investment and the actionable informational gains are the biggest impediments to the installation of more PMUs within the distribution system. A relatively low-cost alternative to many of the commercially available PMUs is the Frequency Disturbance Recorder (FDR), which measures voltage at the 120 V-outlet level. This research proposes using the voltage information obtained from FDRs to validate the benefits of installing PMUs at the distribution level; the work has looked into what system events, both transmission and distribution, can be seen at the distribution level. The thesis begins by providing a background on the state of the distribution system and the effects of new grid technologies. Afterward, the FDR will be introduced, and an example of the information that can be obtained from the data will be shown.\"","Item withdrawn by Laura Spradlin (lspradl2@illinois.edu) on 2014-04-29T21:37:14Z Item was in collections: University of Illinois Theses & Dissertations (ID: 1) No. of bitstreams: 3 Phillips_Desiree.tex: 46401 bytes, checksum: d7dcc8334c3a3d45d383743c7c5c34de (MD5) thesisrefs.bib: 15043 bytes, checksum: 53f7d5a7aef8dca0bcedb0811e78c361 (MD5) Phillips_Desiree.pdf: 3745875 bytes, checksum: 3bab4c5c1b49dcceb399a8155b58b541 (MD5)","Made available in DSpace on 2014-05-30T16:51:49Z (GMT). No. of bitstreams: 4 Desiree_Phillips.pdf: 3745875 bytes, checksum: 3bab4c5c1b49dcceb399a8155b58b541 (MD5) thesisrefs.bib: 15043 bytes, checksum: 53f7d5a7aef8dca0bcedb0811e78c361 (MD5) Phillips_Desiree.tex: 46401 bytes, checksum: d7dcc8334c3a3d45d383743c7c5c34de (MD5) license.txt: 4066 bytes, checksum: eefbf1f3671c30f041e57842777424fc (MD5)"]},{"key":"dc:title","label":"Title","values":["Distribution system analysis using local-area voltage measurements"]}]}],"canonical_facts":{"dc:contributor":["Overbye, Thomas J."],"dc:creator":["Phillips, Desiree"],"dc:date":["2014-05-30T16:51:49Z","2014-05"],"dc:description":["\"The move toward a \"\"smarter\"\" electric grid, along with increased renewable penetration, has motivated the need for increased power system visibility. This is due to the fact that these energy sources introduce transients that previously were not as common or pronounced within the distribution system. Increased distribution system observability can be realized with the implementation of Phasor Measurement Units (PMUs), which measure the AC voltage and current traveling throughout the grid. However, questions related to both the economic investment and the actionable informational gains are the biggest impediments to the installation of more PMUs within the distribution system. A relatively low-cost alternative to many of the commercially available PMUs is the Frequency Disturbance Recorder (FDR), which measures voltage at the 120 V-outlet level. This research proposes using the voltage information obtained from FDRs to validate the benefits of installing PMUs at the distribution level; the work has looked into what system events, both transmission and distribution, can be seen at the distribution level. The thesis begins by providing a background on the state of the distribution system and the effects of new grid technologies. Afterward, the FDR will be introduced, and an example of the information that can be obtained from the data will be shown.\"","Item withdrawn by Laura Spradlin (lspradl2@illinois.edu) on 2014-04-29T21:37:14Z Item was in collections: University of Illinois Theses & Dissertations (ID: 1) No. of bitstreams: 3 Phillips_Desiree.tex: 46401 bytes, checksum: d7dcc8334c3a3d45d383743c7c5c34de (MD5) thesisrefs.bib: 15043 bytes, checksum: 53f7d5a7aef8dca0bcedb0811e78c361 (MD5) Phillips_Desiree.pdf: 3745875 bytes, checksum: 3bab4c5c1b49dcceb399a8155b58b541 (MD5)","Made available in DSpace on 2014-05-30T16:51:49Z (GMT). No. of bitstreams: 4 Desiree_Phillips.pdf: 3745875 bytes, checksum: 3bab4c5c1b49dcceb399a8155b58b541 (MD5) thesisrefs.bib: 15043 bytes, checksum: 53f7d5a7aef8dca0bcedb0811e78c361 (MD5) Phillips_Desiree.tex: 46401 bytes, checksum: d7dcc8334c3a3d45d383743c7c5c34de (MD5) license.txt: 4066 bytes, checksum: eefbf1f3671c30f041e57842777424fc (MD5)"],"dc:identifier":["http://hdl.handle.net/2142/49599"],"dc:language":["en"],"dc:rights":["Copyright 2014 Desiree Phillips"],"dc:subject":["Electric Power System","Distribution System","Distributed Voltage Measurement Unit","Frequency Disturbance Recorder"],"dc:title":["Distribution system analysis using local-area voltage measurements"],"dc:type":["text"],"thesis:degree_discipline":["Electrical & Computer Engr"],"thesis:degree_level":["Thesis"],"thesis:degree_name":["M.S."],"thesis:institution_name":["University of Illinois at Urbana-Champaign"]},"updated_at":"2026-07-22T22:25:38Z"}