{"id":{"repo_id":"uiuc","oai_identifier":"oai:www.ideals.illinois.edu:2142/24063"},"canonical_url":"https://search.dev.ndltd.org/etd/uiuc/oai:www.ideals.illinois.edu:2142/24063","repository":{"repo_id":"uiuc","name":"University of Illinois - Urbana-Champaign","base_url":"https://www.ideals.illinois.edu/oai-pmh"},"display":{"title":"Comparison of refrigerants R410a and R404a for use in low temperature applications: A computer model study","abstract":"The motivation for this thesis is the need for efficient and environmentally friendly refrigerants in low temperature applications. This study provides a perspective for comparison of refrigerant R410a with R404a. As R410a is now widely used commercially, further knowledge is desired on how different an R410a system is from established refrigerant systems and any possibilities for retrofitting. This thesis uses a computer model simulation to specifically compare the performance of R410a and R404a in a supermarket freezer display case system designed for R404a with a standard capacity of 3.42 kW. The computer model is assembled from existing algorithms and correlations for heat transfer, pressure drop, and thermodynamics and run using Engineering Equation Solver (EES). The results are then compared with separate physical experimental results for this exact in-house laboratory refrigeration system. Complimenting the experimental results, the EES model simulates the refrigeration cycle for each refrigerant at four different settings of ambient air temperature into the condenser. The EES model results are compared in graphs and tables to the laboratory results. The model results also show that in this Hussman R404a display case system, R410a still operates more efficiently with a COP generally 0.16-0.19 greater than that of R404a. As expected, R410a operates at a higher compressor discharge pressure and temperature than R404a. After the EES model is verified by comparison to the experimental study, the model is used to predict refrigeration cycle behavior in the case of the heat exchanger component geometry being slightly altered.","abstract_html":"The motivation for this thesis is the need for efficient and environmentally friendly refrigerants in low temperature applications. This study provides a perspective for comparison of refrigerant R410a with R404a. As R410a is now widely used commercially, further knowledge is desired on how different an R410a system is from established refrigerant systems and any possibilities for retrofitting. This thesis uses a computer model simulation to specifically compare the performance of R410a and R404a in a supermarket freezer display case system designed for R404a with a standard capacity of 3.42 kW. The computer model is assembled from existing algorithms and correlations for heat transfer, pressure drop, and thermodynamics and run using Engineering Equation Solver (EES). The results are then compared with separate physical experimental results for this exact in-house laboratory refrigeration system. Complimenting the experimental results, the EES model simulates the refrigeration cycle for each refrigerant at four different settings of ambient air temperature into the condenser. The EES model results are compared in graphs and tables to the laboratory results. The model results also show that in this Hussman R404a display case system, R410a still operates more efficiently with a COP generally 0.16-0.19 greater than that of R404a. As expected, R410a operates at a higher compressor discharge pressure and temperature than R404a. After the EES model is verified by comparison to the experimental study, the model is used to predict refrigeration cycle behavior in the case of the heat exchanger component geometry being slightly altered.","abstract_has_math":false,"creators":["Rajan, Suri"],"institution":"University of Illinois at Urbana-Champaign","degree_name":"M.S.","degree_level":"Thesis","degree_discipline":"Mechanical Engineering","degree_department":null,"school":null,"contributors":["Hrnjak, Predrag S."],"advisors":[],"committee_chairs":[],"committee_members":[],"year":2011,"date_issued":"2011-05-25T14:50:28Z","date_published":"2011-05-25T14:50:28Z","updated_at":"2026-07-22T22:25:23Z","subjects":["R-410A","R-404A","low temperature","refrigeration cycle","Engineering Equation Solver (EES)"],"languages":["en"],"rights":["Copyright 2011 Suri Rajan"],"rights_urls":[],"identifier_entries":[]},"links":{"outbound_url":"http://hdl.handle.net/2142/24063","outbound_label":"Handle","outbound_source":"dc:identifier"},"metadata_groups":[{"id":"people","label":"People","entries":[{"key":"dc:contributor","label":"Contributor","values":["Hrnjak, Predrag S."]},{"key":"dc:creator","label":"Author","values":["Rajan, Suri"]}]},{"id":"academic_context","label":"Academic Context","entries":[{"key":"dc:date","label":"Dc Date","values":["2011-05-25T14:50:28Z","2011-05"]},{"key":"thesis:degree_discipline","label":"Discipline","values":["Mechanical Engineering"]},{"key":"thesis:degree_level","label":"Degree Level","values":["Thesis"]},{"key":"thesis:degree_name","label":"Degree Name","values":["M.S."]},{"key":"thesis:institution_name","label":"Thesis Institution Name","values":["University of Illinois at Urbana-Champaign"]}]},{"id":"subjects_keywords","label":"Subjects and Keywords","entries":[{"key":"dc:subject","label":"Dc Subject","values":["R-410A","R-404A","low temperature","refrigeration cycle","Engineering Equation Solver (EES)"]}]},{"id":"language_rights","label":"Language and Rights","entries":[{"key":"dc:language","label":"Dc Language","values":["en"]},{"key":"dc:rights","label":"Dc Rights","values":["Copyright 2011 Suri Rajan"]}]},{"id":"identifiers","label":"Identifiers","entries":[{"key":"dc:identifier","label":"Identifier","values":["http://hdl.handle.net/2142/24063"]}]},{"id":"additional","label":"Additional Metadata","entries":[{"key":"dc:description","label":"Description","values":["The motivation for this thesis is the need for efficient and environmentally friendly refrigerants in low temperature applications. This study provides a perspective for comparison of refrigerant R410a with R404a. As R410a is now widely used commercially, further knowledge is desired on how different an R410a system is from established refrigerant systems and any possibilities for retrofitting. This thesis uses a computer model simulation to specifically compare the performance of R410a and R404a in a supermarket freezer display case system designed for R404a with a standard capacity of 3.42 kW. The computer model is assembled from existing algorithms and correlations for heat transfer, pressure drop, and thermodynamics and run using Engineering Equation Solver (EES). The results are then compared with separate physical experimental results for this exact in-house laboratory refrigeration system. Complimenting the experimental results, the EES model simulates the refrigeration cycle for each refrigerant at four different settings of ambient air temperature into the condenser. The EES model results are compared in graphs and tables to the laboratory results. The model results also show that in this Hussman R404a display case system, R410a still operates more efficiently with a COP generally 0.16-0.19 greater than that of R404a. As expected, R410a operates at a higher compressor discharge pressure and temperature than R404a. After the EES model is verified by comparison to the experimental study, the model is used to predict refrigeration cycle behavior in the case of the heat exchanger component geometry being slightly altered.","Item withdrawn by Mark Zulauf (zulauf@illinois.edu) on 2011-04-29T14:08:26Z Item was in collections: University of Illinois Theses & Dissertations (ID: 1) No. of bitstreams: 1 Rajan_Suri.pdf: 1044630 bytes, checksum: d59698a1a0213694357f296c8feded07 (MD5)","Made available in DSpace on 2011-05-25T14:50:28Z (GMT). No. of bitstreams: 2 Rajan_Suri.pdf: 1471230 bytes, checksum: 8b80e2d105aead159c64d25731385dad (MD5) license.txt: 4060 bytes, checksum: 3ead0369871f35fac76baf3189174e1b (MD5)"]},{"key":"dc:title","label":"Title","values":["Comparison of refrigerants R410a and R404a for use in low temperature applications: A computer model study"]}]}],"canonical_facts":{"dc:contributor":["Hrnjak, Predrag S."],"dc:creator":["Rajan, Suri"],"dc:date":["2011-05-25T14:50:28Z","2011-05"],"dc:description":["The motivation for this thesis is the need for efficient and environmentally friendly refrigerants in low temperature applications. This study provides a perspective for comparison of refrigerant R410a with R404a. As R410a is now widely used commercially, further knowledge is desired on how different an R410a system is from established refrigerant systems and any possibilities for retrofitting. This thesis uses a computer model simulation to specifically compare the performance of R410a and R404a in a supermarket freezer display case system designed for R404a with a standard capacity of 3.42 kW. The computer model is assembled from existing algorithms and correlations for heat transfer, pressure drop, and thermodynamics and run using Engineering Equation Solver (EES). The results are then compared with separate physical experimental results for this exact in-house laboratory refrigeration system. Complimenting the experimental results, the EES model simulates the refrigeration cycle for each refrigerant at four different settings of ambient air temperature into the condenser. The EES model results are compared in graphs and tables to the laboratory results. The model results also show that in this Hussman R404a display case system, R410a still operates more efficiently with a COP generally 0.16-0.19 greater than that of R404a. As expected, R410a operates at a higher compressor discharge pressure and temperature than R404a. After the EES model is verified by comparison to the experimental study, the model is used to predict refrigeration cycle behavior in the case of the heat exchanger component geometry being slightly altered.","Item withdrawn by Mark Zulauf (zulauf@illinois.edu) on 2011-04-29T14:08:26Z Item was in collections: University of Illinois Theses & Dissertations (ID: 1) No. of bitstreams: 1 Rajan_Suri.pdf: 1044630 bytes, checksum: d59698a1a0213694357f296c8feded07 (MD5)","Made available in DSpace on 2011-05-25T14:50:28Z (GMT). No. of bitstreams: 2 Rajan_Suri.pdf: 1471230 bytes, checksum: 8b80e2d105aead159c64d25731385dad (MD5) license.txt: 4060 bytes, checksum: 3ead0369871f35fac76baf3189174e1b (MD5)"],"dc:identifier":["http://hdl.handle.net/2142/24063"],"dc:language":["en"],"dc:rights":["Copyright 2011 Suri Rajan"],"dc:subject":["R-410A","R-404A","low temperature","refrigeration cycle","Engineering Equation Solver (EES)"],"dc:title":["Comparison of refrigerants R410a and R404a for use in low temperature applications: A computer model study"],"thesis:degree_discipline":["Mechanical Engineering"],"thesis:degree_level":["Thesis"],"thesis:degree_name":["M.S."],"thesis:institution_name":["University of Illinois at Urbana-Champaign"]},"updated_at":"2026-07-22T22:25:23Z"}