The University of Texas at Austin
A voltage-only method for estimating the location of transmission faults
Abstract
dc:description.abstractThis dissertation develops, and illustrates with actual data, a new voltage-only based fault location procedure that incorporates the system impedance matrices into the problem so that as few as three or four voltage recording devices can estimate the fault location over a wide area. This procedure can quickly help pinpoint the fault and complement other available information normally used to manually locate the fault. The second approach takes advantage of the capabilities of microprocessor relays on distribution feeders to reflect their voltage sag measurements back to the transmission system for use with the above algorithm.
Degree
thesis:*- Name thesis:degree_name
- Doctor of Philosophy
- Level thesis:degree_level
- Doctoral
- Discipline thesis:degree_discipline
- Electrical and Computer Engineering
- Grantor
- The University of Texas at Austin
- Year dc:date.issued
- 2006
Author and committee
dc:creator, dc:contributor.*- Author dc:creator
-
- Vatani, Mehrdad
- Advisor dc:contributor.advisor
-
- Grady, W. Mack
Rights
dc:rights- Statement dc:rights
-
- Copyright © is held by the author. Presentation of this material on the Libraries' web site by University Libraries, The University of Texas at Austin was made possible under a limited license grant from the author who has retained all copyrights in the works.
- Language dc:language.iso
- eng
Identifiers
dc:identifier.*- Handle dc:identifier.uri
- http://hdl.handle.net/2152/3509
- OAI identifier oai:identifier
- oai:repositories.lib.utexas.edu:2152/3509