Analysis in circuit breaker performance requirements for high-voltage DC networks

Abstract

dc:description.abstract

Power transmission systems are seeing significant changes with the introduction of large amounts of renewable energy. Integration of these into the network is challenging on two fronts. Firstly, increased penetration stresses conventional generation as those from renewable are intermittent and fluctuate in power output. Secondly, many of these sources are located in areas which are difficult or impossible to economically connect to the network using convention ac technology. This is a major issue for offshore wind where distances to shore are increasing, particularly in the North Sea region. Large scale, multi-terminal high voltage dc networks may offer a solution to these issues, and modern voltage source converters have a small enough footprint to be located on offshore platforms. However, during dc faults these suffer from high currents and the system is unable to transfer power. Prototype dc circuit breakers have been developed by manufacturers to, in theory, allow seamless operation of the healthy areas of the network when a fault occurs. In order to do this they operate extremely fast; opening in less than 5ms. To achieve this the topologies have become complex and expensive, hindering development of multi-terminal systems. In this thesis the requirements of the converter, dc breakers and overall HVDC network are reassessed. The factors influencing stress within the converter and breaker are quantified. Design adjustments which may be used to mitigate these are then investigated. Simplified circuit analysis allows approximations the stresses to calculated and used for initial design iterations. The impact these design alterations has on normal operation is then addressed. A multi-terminal system model is then used to assess how different circuit breaker topologies can effect the fault ride-through of the network. Fault detection and discrimination algorithms are implemented to ensure accurate representation of the time overhead this incurs. It is shown that the variation between slower, cheaper circuit breakers and faster, more costly circuit breakers is not as large as indicated in the current literature. Ride-through for slower circuit breakers is achieved for only a marginal increase in restart time, which is still below the operating speed of conventional ac breakers.

Degree

thesis:*
Name dc:type.qualificationname
phd
Level dc:type.qualificationlevel
doctoral-pg
Grantor dc:publisher.institution
University of Strathclyde
Year dc:date.issued
2016

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Page, Frederick Peter

Identifiers

dc:identifier.*
Identifier
T14353
Author Identifier
201178018
OAI identifier oai:identifier
oai:strathclyde:8p58pd006

Chain of custody

source
Harvested from
University of Strathclyde
Base URL
stax.strath.ac.uk/catalog/oai
Last updated
2026-07-24
Source record
OAI-PMH GetRecord
related terms
citation

Page, Frederick Peter. Analysis in circuit breaker performance requirements for high-voltage DC networks. doctoral-pg thesis, University of Strathclyde, 2016. https://stax.strath.ac.uk/concern/theses/8p58pd006