Back to results

University of Saskatchewan

IMPACT OF HVDC INVERTER STATION FAULTS ON TURBINE-GENERATOR SHAFT TORSIONAL TORQUES

Abstract

dc:description.abstract

The phenomenon of the interaction between turbine-generator shaft systems and the electrical network disturbances has been extensively investigated during the last two decades. Those investigations have shown that some of these disturbances can inflict severe torsional stressing on the shafts of the turbine-generators. The induced high stresses reduce the life expectancy of the turbine-generators and, in severe cases, may cause shaft damages. Besides the electrical network disturbances, turbine-generator shaft torsional systems can interact also with other power system components. These potential sources include power system stabilizers, staticvar compensators, HVDC systems, high-speed governor controls and variable speed drive converters. In most of the reported studies concerned with the interaction of HVDC systems with turbine-generator shafts, attention has been focused on the effect of the HVDC controllers on this phenomenon.Fewer studies have, however, investigated the impact of HVDC converter station and line faults on turbine­ generator shaft torsional torques. This thesis explores the impact of HVDC inverter station faults, namely short circuit across bridge terminals, short circuitacross a non-conducting valve and commutation failureon the torsional torques induced in turbine-generator shafts. The results of these investigations are presented in the form of typical time responses as well as parametric studies. Time domain simulations are carried out using the EMTP. The results of these investigations have demonstrated that inverter station faults including commutation failures excite torsional torques in the turbine-generator shafts. The magnitudes of these torques depend on the initial operating conditions as well as on the fault incidence instant.

Degree

thesis:*
Name thesis:degree_name
Master of Science (M.Sc.)
Level thesis:degree_level
Masters
Discipline thesis:degree_discipline
Electrical Engineering
Grantor
University of Saskatchewan
Year dc:date.issued
2002

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Upadhyay, Sanjoy

Identifiers

dc:identifier.*
Handle dc:identifier.uri
https://hdl.handle.net/10388/11808
OAI identifier oai:identifier
oai:harvest.usask.ca:10388/11808

Chain of custody

source
Harvested from
University of Saskatchewan
Base URL
harvest.usask.ca/server/oai/request
Last updated
2026-07-24
Source record
OAI-PMH GetRecord
related terms
citation

Upadhyay, Sanjoy. IMPACT OF HVDC INVERTER STATION FAULTS ON TURBINE-GENERATOR SHAFT TORSIONAL TORQUES. Masters thesis, University of Saskatchewan, 2002. https://hdl.handle.net/10388/11808