Back to results

Massachusetts Institute of Technology

Demonstration of HVAC chiller control for power grid frequency regulation

Abstract

dc:description.abstract

Secondary frequency regulation is a necessary electric grid ancillary service that balances electric power system supply and demand on short time intervals of seconds to minutes. Commercial HVAC chillers may be well positioned to provide secondary frequency regulation as a demand side resource. Commercial 200 ton (703 kWth) chillers serving two buildings in the Boston area are used to experimentally develop a practical closed-loop controller that modifies chiller power demand to provide secondary frequency regulation. In the first setup, a physical controller is connected directly to the chiller and adjusts power through chilled water setpoint. In the second setup, both the chiller and air handling units are controlled through the BAS. Demonstrations using standard electric system operator test routines show the chiller power response to exceed qualification requirements while providing up to +/-25% of chiller nameplate power in secondary frequency regulation capability. The controller is further demonstrated to provide secondary frequency regulation continuously for several hours longer than the standard test routines, during which building cooling load changes significantly. Analysis of results indicate minimum power and variable COP as two factors that could be incorporated into future models to more accurately reflect observed chiller transient behaviour and predict performance. BAS communication delays, ramp rate limits, and compressor cycling are additional factors that can have significant negative impacts on controller performance. Extrapolation of experiment results to higher-level analysis indicates that chillers can contribute to the secondary frequency regulation requirements at the grid level in aggregate, although potential varies greatly depending on climate and building type. There is more potential in the south, where 21% of secondary frequency regulation requirements might be met with chillers; the contribution of chillers in colder climates is minimal. Short-term power balance to achieve stability is essential for the operation of the modern electrical power system. Providing stability through modified control of existing HVAC chillers in commercial buildings is a technologically feasible alternative to existing solutions and can make a meaningful contribution to the electrical grid.

Degree

thesis:*
Department dc:contributor.department
Massachusetts Institute of Technology. Department of Architecture.
Grantor dc:publisher
Massachusetts Institute of Technology
Year dc:date.issued
2015

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Su, Po-An (Po-An Leo)
Advisor dc:contributor.advisor
  • Leslie K. Norford.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1721.1/99306
OAI identifier oai:identifier
oai:dspace.mit.edu:1721.1/99306

Chain of custody

source
Harvested from
MIT
Base URL
dspace.mit.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
related terms
citation

Su, Po-An (Po-An Leo). Demonstration of HVAC chiller control for power grid frequency regulation. Massachusetts Institute of Technology, 2015. http://hdl.handle.net/1721.1/99306