Back to results

Massachusetts Institute of Technology

Study of airflow and thermal stratification in naturally ventilated rooms

Abstract

dc:description.abstract

Natural ventilation (NV) can considerably contribute to reducing the cooling energy consumption of a building and increase occupant productivity, if correctly implemented. Such energy savings depend on the number of hours that NV can maintain the indoor air temperature within comfort levels. CoolVent, currently the only simple multizone simulation tool that can adequately model the physics of NV in buildings, assumes a uniform temperature distribution in each room or zone. This temperature corresponds to the exhaust air temperature of each room using an energy balance. In reality, however, the air in a room is often thermally stratified, and the air temperature at occupant level can be significantly lower than the exhaust temperature. The final goal of this thesis was to develop a set of criteria to predict the vertical temperature profile in naturally ventilated rooms by comparing the strength of buoyant to inertial forces in the space, based on a few critical room airflow and physical parameters. Developing such criteria required conducting a thorough study of the physics of turbulent jets and plumes, their development in room-sized enclosures, and their effect on the airflow and heat transfer dynamics in a room. Additionally, it was necessary to investigate, using Computational Fluid Dynamics, the effect of certain parameters -such as radiative heat transfer, heat source distribution and room geometry, among others- on the physics of room airflow simulations. Results shed light on the complexity of modeling room airflow and thermal physics analytically, particularly when the air is thermally stratified. Thermal stratification predictions indicate that multi-zone models overestimate the air temperature at occupant height by up to 40% of the total room air temperature change. This work enhances the physical understanding of modeling critical elements of room airflow and improves the predictive accuracy of the natural ventilation potential in buildings. These contributions promote a wider use of passive cooling strategies, thereby increasing the energy efficiency of the built environment.

Degree

thesis:*
Department dc:contributor.department
Massachusetts Institute of Technology. Dept. of Mechanical Engineering.
Grantor dc:publisher
Massachusetts Institute of Technology
Year dc:date.issued
2012

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Menchaca Brandan, María Alejandra
Advisor dc:contributor.advisor
  • Leon R. Glicksman.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1721.1/74907
OAI identifier oai:identifier
oai:dspace.mit.edu:1721.1/74907

Chain of custody

source
Harvested from
MIT
Base URL
dspace.mit.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Menchaca Brandan, María Alejandra. Study of airflow and thermal stratification in naturally ventilated rooms. Massachusetts Institute of Technology, 2012. http://hdl.handle.net/1721.1/74907