Back to results

Massachusetts Institute of Technology

Applied change of mean detection techniques for HVAC fault detection and diagnosis and power monitoring

Abstract

dc:description.abstract

A signal processing technique, the detection of abrupt changes in a time-series signal, is implemented with two different applications related to energy use in buildings. The first application is a signal pre-processor for an advanced electric power monitor, the Nonintrusive Load Monitor (NILM), which is being developed by researchers at the Massachusetts Institute of Technology. A variant form of the generalized likelihood ratio (GLR) change-detection algorithm is determined to be appropriate for detecting power transients which are used by the NILM to uniquely identify the start-up of electric end-uses. An extension of the GLR change-detection technique is used with a second application, fault detection and diagnosis in building heating ventilation and air-conditioning (HVAC) systems. The method developed here analyzes the transient behavior of HVAC sensors to define conditions of correct operation of a computer simulated constant air volume HVAC sub-system. Simulated faults in a water-to-air heat exchanger (coil fouling and a leaky valve) are introduced into the computer model. GLR-based analysis of the transients of the faulted HVAC system is used to uniquely define the faulty state. The fault detection method's sensitivity to input parameters is explored and further avenues for research with this method are suggested.

Degree

thesis:*
Department dc:contributor.department
Massachusetts Institute of Technology. Dept. of Architecture.
Grantor dc:publisher
Massachusetts Institute of Technology
Year dc:date.issued
1995

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Hill, Roger Owen
Advisor dc:contributor.advisor
  • Leslie K. Norford.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1721.1/67272
OAI identifier oai:identifier
oai:dspace.mit.edu:1721.1/67272

Chain of custody

source
Harvested from
MIT
Base URL
dspace.mit.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
related terms
citation

Hill, Roger Owen. Applied change of mean detection techniques for HVAC fault detection and diagnosis and power monitoring. Massachusetts Institute of Technology, 1995. http://hdl.handle.net/1721.1/67272