Fault detection methods for vapor-compression air conditioners using electrical measurements

Abstract

dc:description.abstract

(cont.) This method was experimentally tested and validated on a commercially available air handler and duct system. In the second class of faults studied, liquid refrigerant, rather than vapor, enters the cylinder of a reciprocating compressor during operation. Since the higher cylinder pressures that result can cause substantial damage and are difficult to measure directly, a method for detecting this fault is proposed that only uses observations of the compressor voltage and current. The performance of this fault detection method was also experimentally validated with electrical and mechanical measurements on a semi-hermetic compressor. The final diagnostic method detects refrigerant leakage in a residential air conditioning system by identifying changes in the system's cycling behavior. This method also uses measurements of the compressor's electrical power, as well as a small set of temperature measurements, to determine the presence of the fault. This fault detection method was developed and tested on an occupied residence.

Degree

thesis:*
Department dc:contributor.department
Massachusetts Institute of Technology. Dept. of Architecture.
Grantor dc:publisher
Massachusetts Institute of Technology
Year dc:date.issued
2008

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Laughman, Christopher Reed.
Advisor dc:contributor.advisor
  • Steven B. Leeb, Leslie K. Norford and Peter R. Armstrong.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1721.1/45938
OAI identifier oai:identifier
oai:dspace.mit.edu:1721.1/45938

Chain of custody

source
Harvested from
MIT
Base URL
dspace.mit.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
related terms
citation

Laughman, Christopher Reed.. Fault detection methods for vapor-compression air conditioners using electrical measurements. Massachusetts Institute of Technology, 2008. http://hdl.handle.net/1721.1/45938