This thesis investigates the problem of the Optimal Placement scheme of Phasor Measurement Units in electrical power systems for State Estimation to facilitate improved monitoring and control of the system parameters. The research work done for this thesis begins with review of Supervisory Control and Data Acquisition systems (SCADA). SCADA-based systems are currently employed for condition monitoring and control of industrial and utility electrical power systems. For utility power networks, the main problem with voltage and current phasor data captured by SCADA systems is that they are not synchronised with respect to each other in a present-time or Real-time framework. This implies that both magnitude and phase angle of the measured phasors tend to get affected by slow data flow provided by SCADA to the points of utilization and also by differences in time instants of data capture. These factors inhibit theefficiency and quality of the power system monitoring and control. “Phasor Measurement Unit” (PMU) is a relatively new technology that, when employed in power networks, offers real-time synchronised measurements of the voltages at buses and currents along the lines that connect them. This is accomplished by using a GPS based monitoring system which facilitates time synchronisation of measurements and unlike SCADA, makes the measured data available in Real-Time format. SCADA is not able to provide Real-time data due to the low speeds at which RTUs (Remote Terminal Units) provide data. Availability of time-stamped phasor measurements makes PMUs preferable for power system monitoring and control applications such as State Estimation, Instability Prediction Analysis, Real-time Monitoring of the system conditions, Islanding Detection, System Restoration and Bad Data Detection.

Degree

thesis:*
Grantor dc:publisher.institution
Department of Electrical Engineering
Year dc:date.issued
2013

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Fish, Adbul-Aziz
Advisors dc:contributor.advisor
  • Chowdhury, S
  • Chowdhury, SP

Rights

Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/11427/5223
OAI identifier oai:identifier
oai:open.uct.ac.za:11427/5223

Chain of custody

source
Harvested from
University of Cape Town
Base URL
open.uct.ac.za/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
related terms
citation

Fish, Adbul-Aziz. Optimal placement of phasor measurement units using the Advanced Matrix Manipulation algorithm. Department of Electrical Engineering, 2013. http://hdl.handle.net/11427/5223