Protection Against Ungrounded Single Phase Open Circuit Faults in 3-Phase Distribution Transformers

Abstract

dc:description.abstract

<p>This thesis explores the impacts and behavior of 3-phase distribution transformers when subject to ungrounded single phase open circuit faults. A simple 3-phase system is modeled using MATLAB Simulink and operation under fault conditions are simulated and studied. Simulation results are confirmed via lab experimentation. Finally, a robust detection and protection method using neutral current injection (as proposed in industry literature) is built and demonstrated.</p> <p>Electric utility operating experience has demonstrated that all too often, loads on 3-phase distribution transformers are not adequately protected against an ungrounded single phase open circuit fault (commonly called “single phasing”). This type of fault is amongst the least understood and hence the least protected against. This is especially true at end of transmission system radial feeds where 3-phase transformers can re-create the opened phase voltage due to a variety of effects including magnetic coupling, voltage loops and loading effects. Operating experience in the nuclear power industry has shown that the results can be catastrophic especially considering the impacts to motor loads. Impacts can result in unavailability of emergency loads, tripping of motor protection circuits or even motor damage and failure.</p>

Degree

thesis:*
Name thesis:degree_name
MS in Electrical Engineering
Discipline thesis:degree_discipline
Electrical Engineering
Year dc:date.available
2018

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Montoya, Higinio Ariel
Contributors dc:contributor
  • Ali Shaban

Subjects

dc:subject × 6

Identifiers

dc:identifier.*
OAI identifier oai:identifier
oai:digitalcommons.calpoly.edu:theses-3145

Chain of custody

source
Harvested from
Cal Poly
Base URL
digitalcommons.calpoly.edu/do/oai/
Last updated
2026-07-24
Source record
OAI-PMH GetRecord
citation

Montoya, Higinio Ariel. Protection Against Ungrounded Single Phase Open Circuit Faults in 3-Phase Distribution Transformers. 2018. https://digitalcommons.calpoly.edu/theses/1869