dc:description.abstract

Evaluation and comparison of two methods for voltage stability assessment in power systems. They are the Topological Monitoring Method Duong (MBTDUONG) and the Adaptive Identification Method Corsi-Taranto (MBM-CT). Both algorithms have a characteristic of using phasor measurements from PMUs to make their estimates, which are based on the determination of the Thevenin equivalents of the load buses to be analyzed, comparing the values obtained with the impedance values of these ones. Thus, using the Maximum Power Transfer Theorem, a proximity of the voltage instability will be associated with the moment of the impedance matching. Their performance is analyzed for different load modeling, actuation of over-excitation limiters (OELs), actuation of on load tap changers (OLTCs), systemic contingency and limitation of active generation (turbine limits). The simulations were performed in two systems: 3-Bus System and WSCC 9-Bus System. The simulation is performed in the time domain, using the power system analysis toolbox PSAT for Matlab.Também disponível on-line.

Degree

thesis:*
Grantor dc:publisher
Universidade Federal do Rio de Janeiro
Year dc:date.issued
2017

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Ferreira, Alan de Paula Faria
Advisor dc:contributor.advisor
  • Taranto, Glauco Nery

Subjects

dc:subject × 3

Rights

dc:rights
Statement dc:rights
  • Acesso Aberto
Language dc:language
por

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/11422/6100
OAI identifier oai:identifier
oai:pantheon.ufrj.br:11422/6100

Chain of custody

source
Harvested from
Brazil UERJ
Base URL
pantheon.ufrj.br/oai/request
Last updated
2026-07-24
Source record
OAI-PMH GetRecord
citation

Ferreira, Alan de Paula Faria. Comparação de dois métodos de detecção da instabilidade de tensão baseados em medição fasorial e equivalente de Thévenin. Universidade Federal do Rio de Janeiro, 2017. http://hdl.handle.net/11422/6100