Global ETD Search

Search theses and dissertations gathered from participating repositories worldwide. Every result links back to the library that holds it. No account is needed.

Results

Showing 1 to 1 of 1 for “"coal electrical safety"”.

  1. Improvement of Ground-Fault Relaying Selectivity through the Application of Directional Relays to High-Voltage Longwall Mining Systems

    … improve ground-fault relaying selectivity. A safety analysis considering the potential for electrocution and the power dissipated by the maximum fault resistance showed that increasing the pick-up setting by a factor of eight would have no detriment to safety. Therefore, either method would …

    vt Repository record for Improvement of Ground-Fault Relaying Selectivity through the Application of Directional Relays to High-Voltage Longwall Mining Systems (opens in a new tab)