Back to search

Virginia Tech

Power transformer magnetization under GIC/GMD

Abstract

dc:description.abstract

Geomagnetically induced currents (GIC) could saturate a transformer core. Two significant effects are the abnormal stray flux in transformers and extremely large harmonic contents in excitation currents, which can lead to serious equipment damage and power system misoperation. Such incidents have occurred during the March 1989 K-9 solar magnetic disturbance. This dissertation starts with a systematically study of transformer magnetization under GIC. It reviews both dc and ac saturation patterns of five transformer core designs. Magnetic fields along various traverses for dc excitation are presented. Impedance matrix entries of a single phase transformer are compared for normal and dc operations. New observations have been formed based on the simulation results. The study helps to reveal the fundamental transformer magnetization mechanism under GIC in order to assess potential stray flux heating possibilities of geologically vulnerable transformer units. Based on the finite element analysis, an improved method of modeling transformer excitation under dc bias using equivalent magnetic circuit is developed. There are two unique points in this approach: first, information of 3D finite element magnetic flux distribution analysis is used to construct and verify the circuit model; second, the effect of the transformer tank: is included The model is capable of simulating transformer excitation currents under different levels of dc bias with good accuracy. As a consequence, the complete variations of excitation current harmonics with respect to an extended range of dc bias are revealed. The sensitivity of transformer winding impedances and core loss on the excitation characteristics are examined. The saturated transformer under no-load and various loading conditions is simulated. A laboratory test is performed on a small scale transformer and compared with the model results. Excitation harmonics generated from dc biased three phase transformer banks with different types of equivalent loads are also simulated The effect of both unbalanced dc excitations and unbalanced loads are investigated The results of this study contribute in understanding transformers as harmonic sources and the impact on power systems during a geomagnetic disturbance.

Degree

thesis:*
Name thesis:degree_name
Ph. D.
Level thesis:degree_level
doctoral
Discipline thesis:degree_discipline
Electrical Engineering
Department dc:contributor.department
Electrical Engineering
Grantor dc:publisher
Virginia Tech
Year dc:date.issued
1994

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Lu, Shu
Chair dc:contributor.committeechair
  • Liu, Yilu
Committee members dc:contributor.committeemember
  • Phadke, Arun G.
  • Besieris, Ioannis M.
  • De La Ree, Jaime
  • Johnson, Lee W.

Rights

dc:rights
Statement dc:rights
  • In Copyright
Language dc:language.iso
en

Identifiers

dc:identifier.*
Dc Identifier Other
etd-09232008-144706
OAI identifier oai:identifier
oai:vtechworks.lib.vt.edu:10919/39460

Chain of custody

source
Harvested from
Virginia Tech
Base URL
vtechworks.lib.vt.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
related terms
citation

Lu, Shu. Power transformer magnetization under GIC/GMD. doctoral thesis, Virginia Tech, 1994. http://hdl.handle.net/10919/39460