Advancing the Understanding of Water Distribution System Corrosion: Effects of Chlorine and Aluminum on Copper Pitting, Temperature Gradients on Copper Corrosion, and Silica on Iron Release

Abstract

dc:description.abstract

When severe copper pitting problems impacted customers at a large utility, studies were begun to attempt to diagnose the problem and identify potential solutions. A series of tests were conducted to characterize the nature of pitting. Desktop comparisons of pinhole leak frequency and treatment practices at nearly utilities were also documented to identify treatment factors that might be influencing the initiation and propagation of leaks. Factors identified included the presence of relatively high levels of free chlorine and aluminum in the distribution system. Experiments were conducted to examine the effect of these constituents on copper pitting under stagnant and flow conditions. That led to discovery of a synergistic redox reaction between chlorine, aluminum solids, and copper metal as evidenced by increased chlorine decay rates, non-uniform corrosion, and rising corrosion potentials. Temperature changes had been suspected to increase copper pitting frequency and copper release to drinking water. Experiments examined the effect of temperature gradients on copper pipe corrosion during stagnant conditions. The pipe orientation in relation to the temperature gradient determined whether convective mixing would occur, which influenced temperature gradients within the pipe. This work is the first to demonstrate that temperature gradients lead to thermogalvanic currents, influences copper leaching and scale type. Iron release from corroding water mains is another concern of many water utilities, but little is known about chemistry factors that influence the problem. In laboratory experiments, higher levels of silica caused more iron release to the water and decreased the size of suspended iron particles. Silica levels also changed during the experiment: it decreased through incorporation into a dense scale, and increased by release from cast iron during corrosion. Silica slightly decreased iron corrosion rates near the end of this 6-month test.

Degree

thesis:*
Name thesis:degree_name
Master of Science
Level thesis:degree_level
masters
Discipline thesis:degree_discipline
Environmental Planning
Department dc:contributor.department
Environmental Engineering
Grantor dc:publisher
Virginia Tech
Year dc:date.issued
2002

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Rushing, Jason Clark
Chair dc:contributor.committeechair
  • Edwards, Marc A.
Committee members dc:contributor.committeemember
  • Novak, John T.
  • Vikesland, Peter J.

Subjects

dc:subject × 9

Rights

dc:rights
Statement dc:rights
  • In Copyright

Identifiers

dc:identifier.*
Dc Identifier Other
etd-07292002-124850
OAI identifier oai:identifier
oai:vtechworks.lib.vt.edu:10919/34235

Chain of custody

source
Harvested from
Virginia Tech
Base URL
vtechworks.lib.vt.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Rushing, Jason Clark. Advancing the Understanding of Water Distribution System Corrosion: Effects of Chlorine and Aluminum on Copper Pitting, Temperature Gradients on Copper Corrosion, and Silica on Iron Release. masters thesis, Virginia Tech, 2002. http://hdl.handle.net/10919/34235