Experimental and Analytical Investigation of the Transient Thermal Response of Air Cooled Data Centers

Abstract

dc:description.abstract

<p>This work investigates the transient response of the thermal environment in air cooled data centers through experiments, analytical and computational tools. The key thermal characteristics of the various data center components were extracted from a set of experiments. This includes the development of practical experimental procedures for the thermal characterization of servers solely based on air temperature measurements and the transient response of the computer room air handlers. The knowledge of thermal characteristics paves the way for the physics-based lumped-capacitance models. A CFD-based transient simulation of the air temperature field, in which the transient thermal response of the servers was included via user-defined functions failed to predict the time-dependent server inlet temperature with acceptable accuracy and highlighted the need for including the thermal capacitance and heat transfer characteristics of the entire room, not just the servers. Hence, a practical faster-executing hybrid lumped capacitance-CFD/Experimental model was developed to investigate the thermal response of data centers under certain scenarios of cooling interruption, server shutdown and cooling air flow changes. Beyond the servers, the model takes into account the effect of the air volume, the building materials of the room and plenum and the CRAH units. The model is capable of predicting server inlet temperatures to within the experimental uncertainty (±1°C) with inputs that are relatively easy to obtain in a production data center.</p>

Degree

thesis:*
Name thesis:degree_name
Doctor of Philosophy (PhD)
Level thesis:degree_level
Dissertation
Discipline thesis:degree_discipline
Mechanical and Aerospace Engineering
Year
2013

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Erden, Hamza Salih
Contributors dc:contributor
  • H. Ezzat Khalifa
  • Can Isik

Subjects

dc:subject × 7

Identifiers

dc:identifier.*
Repository record dc:identifier
https://surface.syr.edu/etd/43
OAI identifier oai:identifier
oai:surface.syr.edu:etd-1043

Chain of custody

source
Harvested from
Syracuse University
Base URL
surface.syr.edu/do/oai/
Last updated
2026-07-24
Source record
OAI-PMH GetRecord
citation

Erden, Hamza Salih. Experimental and Analytical Investigation of the Transient Thermal Response of Air Cooled Data Centers. Dissertation thesis, 2013. https://surface.syr.edu/etd/43