Back to search

Massachusetts Institute of Technology

Analysis of buoyancy driven airflow patterns in a model of a naturally ventilated building

Abstract

dc:description.abstract

Models can help us understand the climate conditions inside naturally ventilated buildings in order to improve the efficiency of the design. Naturally ventilated buildings use temperature gradients to create buoyancy forces in the space and drive the airflow pathways in the space. One architectural design feature that facilitates natural ventilation is the presence of stack ventilation in the roof of the building, which facilitates the expulsion of heated air from the space. An architectural feature that changes the airflow pathways is the presence of railing on the upper floors where there is a danger of falling into the atrium. Using the model of a naturally ventilated building located in the Building Technology Department at MIT airflow visualization studies were carried out using incense to view the airflow patterns in the model. The variables of temperature, size of stack ventilation opening, and whether there were railings in the building or not were varied to determine their effects on the airflow. Temperature had the effect of increasing the velocity of the airflow, but did not significantly change the overall airflow profile. The size of the stack vent opening changed the airflow pathways significantly as did adding railings into the model. Comparing the results with a computational fluid dynamics model shows that there are some discrepancies.

Degree

thesis:*
Department dc:contributor.department
Massachusetts Institute of Technology. Dept. of Mechanical Engineering.
Grantor dc:publisher
Massachusetts Institute of Technology
Year dc:date.issued
2004

Author and committee

dc:creator, dc:contributor.*
Author dc:creator
  • Cain, Melissa, 1982-
Advisor dc:contributor.advisor
  • Leon Glicksman.

Subjects

dc:subject × 1

Rights

dc:rights
Statement dc:rights
  • M.I.T. theses are protected by copyright. They may be viewed from this source for any purpose, but reproduction or distribution in any format is prohibited without written permission. See provided URL for inquiries about permission.
Language dc:language.iso
eng

Identifiers

dc:identifier.*
Handle dc:identifier.uri
http://hdl.handle.net/1721.1/32797
OAI identifier oai:identifier
oai:dspace.mit.edu:1721.1/32797

Chain of custody

source
Harvested from
MIT
Base URL
dspace.mit.edu/oai/request
Last updated
2026-07-22
Source record
OAI-PMH GetRecord
citation

Cain, Melissa, 1982-. Analysis of buoyancy driven airflow patterns in a model of a naturally ventilated building. Massachusetts Institute of Technology, 2004. http://hdl.handle.net/1721.1/32797